How to Calculate OBC Snow Load: The Part 9 Formula Explained

Every roof in Ontario has to hold up more than its own weight. It has to hold up winter. The Ontario Building Code turns that reality into a number — the specified snow load — and that number drives everything downstream: which span table row applies, how big a beam needs to be, and whether a roof design passes or fails. For BCIN candidates, it's also one of the few structural calculations that shows up again and again across the technical exams, because so much else depends on getting it right first.

This guide walks through how the Code actually calculates snow load for Ontario buildings, why houses use a simpler version of the formula than larger buildings do, and where the climate data behind it comes from. If you've already worked through Tempr's BCIN exam prep course or our guide on reading OBC span tables, this fills in the piece those tables assume you already have: the snow load value itself.

Two Formulas, Two Parts of the Code

The Ontario Building Code doesn't calculate snow load the same way for every building. Division B splits the job between two parts, and knowing which one applies is itself a common exam trap.

Part 4 (Structural Design) sets out the general-purpose formula, in Article 4.1.6.2, Sentence (1):

S = Is × [Ss(Cb·Cw·Cs·Ca) + Sr]

Each term adjusts the load for a different variable:

That's a lot of moving parts, and it's meant for exactly that: engineered buildings, unusual roof shapes, and anything that falls outside the prescriptive scope of Part 9.

The Simplified Formula for Houses

Part 9 (Housing and Small Buildings) takes a different approach. Because Part 9 only governs buildings of a limited, well-understood type — essentially traditional low-rise residential construction within Part 9's size and occupancy limits — the Code doesn't make designers work through importance, wind exposure, and accumulation factors every time. Article 9.4.2.2 gives a simplified formula instead, in Sentence (1):

S = Cb × Ss + Sr

Here, Cb collapses down to just two possible values, based on roof width:

Sentence 9.4.2.2.(2) also sets a floor: in no case shall the specified snow load be less than 1 kPa, even in parts of the province where the formula alone would produce a smaller number. And Sentences (3) through (5) carve out exceptions for long-span bowstring, arch, or semi-circular trusses, and for extra load near roof steps — both of which push a project back toward Part 4-style engineering judgment rather than the simple formula.

The practical takeaway for exam purposes: if the building is a Part 9 house or small building, you almost always use the two-term formula with one of two Cb values, not the full Part 4 version with four separate factors. Reaching for Is, Cw, Cs, and Ca on a straightforward Part 9 house is a sign you're in the wrong subsection.

Where Ss and Sr Actually Come From

Neither formula tells you what Ss or Sr equal — those are climate-dependent, and the Code doesn't put them in Part 4 or Part 9 at all. Instead, both formulas point to Supplementary Standard SB-1 (Climatic and Seismic Data), in Volume 2 of the Code. SB-1's Table 2 lists the 1-in-50-year ground snow load (Ss) and associated rain load (Sr) for more than 230 named locations across Ontario, organized alphabetically, along with elevation, design temperatures, rainfall, and several other climate values used elsewhere in the Code.

These values genuinely are local. A city on Georgian Bay's snowbelt and a city on the north shore of Lake Erie can carry meaningfully different design loads, which is exactly why the Code looks the number up by location instead of specifying one province-wide figure. That also means you can't memorize "the" ground snow load for Ontario — you look up the right row for the project's municipality (and sometimes a specific zone within a large municipality, since a few cities are split into sub-areas) every time. Always confirm you're reading the SB-1 table from the Code edition that actually governs the project, since climatic values can be revised between editions.

A Worked Example

Say a Part 9 house is being designed with a gable roof 9 m wide, in a municipality where SB-1 lists a ground snow load (Ss) of 2.4 kPa and an associated rain load (Sr) of 0.4 kPa.

Because the roof width is greater than 4.3 m, Cb = 0.55. Plugging into the Part 9 formula:

S = (0.55 × 2.4) + 0.4 = 1.32 + 0.4 = 1.72 kPa

That's above the 1 kPa minimum, so 1.72 kPa is the specified snow load — the number you'd then carry into the roof span tables to size rafters or trusses. If the same house sat in a lighter-snowfall part of the province where Ss and Sr were both smaller, the formula could produce a result below 1 kPa — and in that case, the 1 kPa floor would take over as the governing value instead. The arithmetic is simple; the part worth double-checking is always the inputs: the right Cb breakpoint, the right SB-1 row for the actual site, and the floor value.

Common Exam Traps

A few mistakes show up repeatedly in practice questions and in real permit submissions alike:

Snow load is a short calculation once you know which formula to reach for and where the inputs come from — but it sits upstream of span tables, truss design, and a good portion of Part 9 and Part 4 structural questions on the BCIN exams. If you want to work through it alongside other structural compliance topics with guided practice and an AI tutor, Tempr's Ontario Building Code Structural Compliance course is built on the current 2024 OBC, and new students can try it free for three months with no credit card required.